Amana Air Conditioner Error Code

Amana PBC092E00AX air error codes

CODESTATUSCORRECTIVE ACTION
F1Outdoor ambient thermostat not registering on the board.Replace or re-connect the thermostat
F2Outdoor ambient thermostat not registering on the board.Replace or re-connect the thermostat
F4Outdoor coil thermostat not rgistering on the boardReplace or re-connect the thermostat
FJIndoor discharge thermostat not registering on the boardReplace or re-connect the thermostat

Amana SC-415 air error codes

Configuration CodeDescriptionDescription
C1InterfaceChassis Membrane*
Wireless Remote
Wired Thermostat
C2Fan OperationButton present
7-Button, reverts to Cyclic
Always run fan (even in Off)
7-Button, revets to Continuous
C3Reverse Cycle OperationCooler Only
Heat Pump*
Sevice No Operation "Eo"
C4Room I.D. Digit 1 & 200* - 99
C5Room I.D. Digit 3 & 400*-99
C6Wired OccupancyOff*
18 Hour Automatic Entry
C8Temp. Limiting Cool60*-72
C9Temp. Limiting Heat68 - 90, 80*
CdEnglish / Metric TempFahrenheit Scale*
Celsius Scale
d6Sensor less Un-Occ. Time1 - 32, 18*
d71st Un-Occ. Set Back Temp.1 - 16, 2*
d81st Un-Occ. Set Back Time.1 ,.5,1-24, .5*
d92nd Un-Occ. Set Back Temp.1 - 16, 3*
dA2nd Un-Occ. Set Back Time(d8) - 24, 1*
db3rd Un-Occ. Set Back Temp.1 - 16, 6*
dC3rd Un-Occ. Set Back Time(dA) - 24, 3*
dFJace Group Code00* - 99
r4Room Prefix00*-99
r5Room Suffix00*-99

Amana DigiSmart PTC074E25AXXX air error codes

CODESTATUSDISPLAYERROR LIGHTSUGGESTED ACTION
FPFreeze Protection Engaged. The room temperature measured by the wireless remote thermostat or indoor ambient thermistor active sensor falls below 40°F.YNNo Action required. This setting will disengage when the room temperature rises above 43°F.
FdFront Desk switch is closed. All outputs are switched off.YNOpen front desk switch to alow occupant unit operation.
EoUn-Configured Service Board -YYEnter Configuration Menu and set "C3" to "C" for coolers with electric heat or "H" for heat pumps.
All operation held awaiting configuration
EHEmergency Hydronic Engaged. The EHH swіtch is closed. Compressor is switched off.YNOpen front emergency hydronic switch to allow occupant unit operation.
LSLoad Shedding Engaged. The LS switch is closed. Compressor and Electric heat is switched off.YNOpen toad shedding switch to allow occupant unit operation.
OnControl is configured to respond to a wired thermostatYNNo action if a wired thermostat is being used. Otherwise, see Configuration Settings.
OPOpen Door LockoutYYClose Room Door.
(DS1 & DS2 open: wireless)Unit wll not condition space with door open.
nPWindow Switch Lockout -YYClose Room Door or Window.
(LS & INN open)Unit wil not condition space with door or wndow open.
hPHeat Sentinel -YNNo action required. This setting will disengage when the room temperature falls.
(WIAT > u3)
UrUn-Rented StatusYNFront Desk needs to set to Rented mode (if applicable).
(EHH & INN or wireless)
F1Indoor Ambient Thermistor reads outside the range -20°F to 200°F & the wireless thermostat is not communicating to the unit control orYYReplace black Indoor Ambient Thermistor or Wireless Remote Thermostat.
Indoor Ambient Thermistor (IAT) without a wireless remote thermostat reads outside the range -20°F to 200°F.
F2Wireless Remote Thermostat failureNNReplace Wireless Thermostat.
F3Indoor Ambient Thermistor reads outside the range -20°F to 200°FYNReplace black Indoor Ambient Thermistor.
F4Indoor Coi Thermistor either above or below operating tolerances.NYReplace Red Indoor Coil Thermistor.
F5Wireless Thermostat faiure.NYAttempt to rebind Wireless Thermostat or Replace Wireless Thermostat.
F6Indoor Discharge Thermistor ether above or below operating tolerances.NYReplace Yelow Indoor Discharge Thermistor.
FbLow Remote Battery Warning.NYReplace Batteries in Wireless Devices.
H1High Voltage Protection engaged. Power supply voltage is to high.YNCheck for incoming power at correct voltage.
brBrown Out Protection engaged. Power was tost or voltage is low.NNCheck for incoming power at correct voltage.
L6Discharge Air Too Hot.NYClean Filter or Remove Air Blockage.
LCOutdoor Coil Thermistor temperature high.NYClean Condenser Coils, Check Fan for fault. Code wil reset after cleaning.
C2Indoor Air Recirculation. Large delta between thermostat and return.NYClean Filter or Remove Air Blockage or Close Vent Door or Improve indoor to outdoor seal.
C5Outdoor Coil temperature too high for outdoor ambient temperature.NYCheck for Blocked Outdoor Air or Clean Coil.
C1Indoor Coil is freezing up.NYClean fіlter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capilary tube.
C3Indoor Coil is freezing up.NYClean fіlter. Check for fan and blower operation, Check for Refrigerant loss or Restricted capilary tube.
C4Indoor Coil froze up.NYClean fіlter. Check for fan and blower operation, Check for Refrigerant loss or Restricted capilary tube.
C6Poor Unit Performance.NYCheck for blower motor, compressor, or electric heat operation.
C7Indoor Freezing Lockout (ICT - IAT > 20) +10 MinNYClean flter. Check for fan and blower operation, Check for Refrigerant loss or Restricted capilary tube.